Old 08-09-2006, 09:31 AM  
RustyShack
RustyShackleford
 
Join Date: Aug 2006
Posts: 5
Default Gas Heater

i have a 32'x 28' with 7' ceiling. this space has some heat from main furnace in house but i would like to add a gas stove for more heat as i live down there. gas pipe connection already there. approx how many btu's do i need?
also, i would also like to know if vent-free stove is a good choice and if anyone can recommend a good product?



__________________
RustyShack is offline  
 
Reply With Quote Quick reply to this message
Old 08-09-2006, 08:34 PM  
inspectorD
Housebroken
HRT_MODERATOR.png
 
inspectorD's Avatar
 
Join Date: Dec 2005
Location: Litchfield, CT
Posts: 3,929
Liked 87 Times on 76 Posts
Likes Given: 184

Default Never....

Never , ever ever ever .............

Do not use a vent free stove. there is no such thing.....

We would love for you to stay around .

Carbon monoxide is a deadly killer that WILL build up in you home with these stoves. It has to be one of the dumbest inventions anyone has ever thought of.
Must have been a marketing guy.

Let him stick his head in the oven.
Any stove company can help with sizing the unit to your home. better yet get 3 stove companies advice.

Good luck.

Can you tell I don't like ventless.



__________________

Just My
Made in the

inspectorD is offline  
 
Reply With Quote Quick reply to this message
Old 08-09-2006, 09:05 PM  
glennjanie
Senior Member
 
Join Date: Mar 2006
Posts: 2,992
Liked 2 Times on 2 Posts

Send a message via AIM to glennjanie
Default

Well InspectorD
I don't want to rain on your parade but gas heat has come a long way in the last few years. Ventless logs and stoves work just fine and they have a sensor on them that shuts them down if the air goes funky. I have been using ventless gas logs for 8 or 10 years now and we are all still kickin'. If a person has apprehensions about it they can put up a carbon monoxide monitor/alarm.
Glenn

__________________
glennjanie is offline  
 
Reply With Quote Quick reply to this message
Old 08-09-2006, 09:06 PM  
Square Eye
Senior Member
 
Square Eye's Avatar
 
Join Date: Jan 2006
Posts: 1,273
Liked 4 Times on 4 Posts

Default

InspectorD, you got something against carbon monoxide?

__________________

[URL="http://www.houserepairtalk.com/announcement.php?f=39&a=6"][size=3]The Ten Commandments of House Repair Talk[/size][/URL]



[URL="http://home.bellsouth.net/p/s/community.dll?ep=16&groupid=289528&ck="]Square Eye's home page[/URL]

Square Eye is offline  
 
Reply With Quote Quick reply to this message
Old 08-10-2006, 05:58 AM  
RustyShack
RustyShackleford
 
Join Date: Aug 2006
Posts: 5
Default

Thank you for opinions. there is a web-site for Rinnai.us/ ventless gas heaters and all seems ok, but either way how many BTU's should i be looking for....

__________________
RustyShack is offline  
 
Reply With Quote Quick reply to this message
Old 08-10-2006, 10:07 AM  
RustyShack
RustyShackleford
 
Join Date: Aug 2006
Posts: 5
Default

i will do vent-free but please how many BTU's for this room? 5,000, 10,000 how many to be comfortable and not overpowering ????????

__________________
RustyShack is offline  
 
Reply With Quote Quick reply to this message
Old 08-10-2006, 03:24 PM  
glennjanie
Senior Member
 
Join Date: Mar 2006
Posts: 2,992
Liked 2 Times on 2 Posts

Send a message via AIM to glennjanie
Default

Hi Rusty:
If the room is well insulated and not on the NorthWest corner of the house I would think a 50,000 btu unit would work well. If the qualifications are not there it may take more like 80 to 100,000 btu. Like InspectorD said the dealers will be happy to size it for you. For economical operation it is best to stay on the low side, whereas the unit would run full time on the worse days and might even loose 2 to 5 degrees but would cycle on and off on milder days. Of course, your location probably gets more extreme cold days than I would ever imagine. Your best shot is, talk to the dealers.
Glenn

__________________
glennjanie is offline  
 
Reply With Quote Quick reply to this message
Old 08-10-2006, 05:30 PM  
inspectorD
Housebroken
HRT_MODERATOR.png
 
inspectorD's Avatar
 
Join Date: Dec 2005
Location: Litchfield, CT
Posts: 3,929
Liked 87 Times on 76 Posts
Likes Given: 184

Default Problem? me.................

I just do not trust the people that dont maintain their units. I also have come across a few folks that don't read or use the directions which say you need a fresh source of air.
What do you mean I need to keep the window cracked ....that lets in the cold air!!! Or the folks that dont clean......
Many times I have turned on the Ventless units only to see my CO detector go off the walls!! No unit is perfect....and I know everyone gets a new CO detector every 7 years, or even changes the batteries. Or when the power goes out and the sensors still don't work...take the chance? Hmmmmmmm........

So yea ...I dont like em.

Just get a vented unit. It should be a no brainer, they are easy to pipe now.....unless you like CO.

Also like glennjanie said...get a new CO detector.



__________________

Just My
Made in the

inspectorD is offline  
 
Reply With Quote Quick reply to this message
Reply


Quick Reply
Message:
Options

Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter DIY Home Repair Forum Replies Last Post
Can I somehow disable the 'water heater' in my summer winter hookup? Mick HVAC 1 12-13-2008 06:30 AM
How to Move a Hot Water Heater clemkonan Plumbing Forum 3 11-14-2008 01:13 PM
Looking to buy a more efficient Water Heater 82-T/A General Appliance Discussion 1 07-03-2008 07:36 AM
Hot Water Heater guyod Plumbing Forum 6 01-24-2008 11:57 AM
newbie post-- house heater question mustangbaxter HVAC 3 01-28-2007 07:59 AM