Default Hole in copper line

In the process of pulling a wire off the contactor of a Goodman mini split which has 115Volt control wiring, the spade connector hit a copper tube and punched an electrical hole in it. Naturally the Freon (or what ever they call it these days) left the system.

The question is, how do you solder the hole shut? I've always heard that silver solder was used for A/C units. I have soldered a lot of copper plumbing back in the day and done a lot of circuit board soldering, but silver soldering is something I'm gonna need help with.

Can somebody point me in the right direction?

If we get this straightened out, then maybe I can start a new thread about the reversing valve that doesn't reverse anymore.

Thanks in advance...



__________________
FAQ's
Speedbump is offline  
 
Reply With Quote Quick reply to this message
Old 08-17-2010, 11:46 AM  
kok328
Supporting Member
HRT_SUPPORTER.png
 
Join Date: Nov 2007
Location: Grand Blanc, MI
Posts: 2,168
Liked 100 Times on 88 Posts
Likes Given: 61

Default

You are going to have to braze it with silver rod. These lines can see 300psi.



__________________
kok328 is offline  
 
Reply With Quote Quick reply to this message
Old 08-17-2010, 06:30 PM  
Speedbump
Water well etc.
 
Speedbump's Avatar
 
Join Date: Apr 2009
Location: Riverview, Fl.
Posts: 422
Liked 21 Times on 20 Posts
Likes Given: 1

Default

Can you give me some hints on how to do the silver solder thing. I've never done it before.

__________________
FAQ's
Speedbump is offline  
 
Reply With Quote Quick reply to this message
Old 08-18-2010, 05:07 AM  
kok328
Supporting Member
HRT_SUPPORTER.png
 
Join Date: Nov 2007
Location: Grand Blanc, MI
Posts: 2,168
Liked 100 Times on 88 Posts
Likes Given: 61

Default

It's basically just like soldering or more like stick welding. You'll need a Oxy-Acetylene Welding & Brazing torch and some silver rod. For complete and accurate steps, you may google "HVAC Oxy-Acetylene brazing". However, being that all the freon has left your system, your going to need someone to perform evac and recharge procedures and for them to braze a small hole before doing so really shouldn't add to the cost of the recharge. It might be better just to let the HVAC tech take care of that for you.
Good Luck.

__________________
kok328 is offline  
 
Reply With Quote Quick reply to this message
Old 08-18-2010, 05:16 AM  
budro
Member
 
Join Date: Aug 2010
Posts: 77
Default

assuming you have a acetylene/oxygen set i would probably get a little extra copper and practice on it. i know it is expensive but if you have some or know someone with some extra tubing and are determined to do it yourself that might be a good idea. if you are not comfortable with this type of torch get a pro to do it even though it won't take him five minutes. if not done properly you can easily blow a large hole in the pipe. with this type of torch you can't just put the flame to the copper and heat it up like a propane torch. i believe there are several thousands of degrees of heat difference between propane and a/o torches. you can quickly damage your body and your wallet here. be safe. thanks, buddy

__________________
budro is offline  
 
Reply With Quote Quick reply to this message
Old 08-18-2010, 05:21 AM  
budro
Member
 
Join Date: Aug 2010
Posts: 77
Default

kok328 is right on target. the tech performing the other tasks is going to be your brazing pro. best to let him handle it. thanks, buddy

__________________
budro is offline  
 
Reply With Quote Quick reply to this message
Old 08-18-2010, 06:47 AM  
Speedbump
Water well etc.
 
Speedbump's Avatar
 
Join Date: Apr 2009
Location: Riverview, Fl.
Posts: 422
Liked 21 Times on 20 Posts
Likes Given: 1

Default

The guy that will vacuum the lines and put in the new freon is a friend of mine, but I'm not sure he has ever done this before.

I do have Oxy/Acetylene torches and know how to use them. I guess a Turbo torch isn't hot enough then... Right?

Using a silver stick, do you need any kind of flux or acid or do you just clean the copper like you would to do a plumbing repair?

I've done lots of brazing and welding using torches, so it's not new to me. Although the idea of practicing first is a great idea and I will do exactly that.

__________________
FAQ's
Speedbump is offline  
 
Reply With Quote Quick reply to this message
Old 09-11-2010, 09:42 AM  
oldman55
Junior Member
 
Join Date: Nov 2007
Location: Marion,In., Indiana
Posts: 7
Default

if you are going to do any brazing on refrigerant lines you need to run nitrogen through the lines to keep them from scaling. you also should either change or replace the filter drier. if you don't you stand a chance of moisture being in the system or scaling coming loose and causing a blockage.

__________________
oldman55 is offline  
 
Reply With Quote Quick reply to this message
Old 09-11-2010, 02:19 PM  
Speedbump
Water well etc.
 
Speedbump's Avatar
 
Join Date: Apr 2009
Location: Riverview, Fl.
Posts: 422
Liked 21 Times on 20 Posts
Likes Given: 1

Default

Thanks, but I'm still trying to figure out how to do the soldering.

__________________
FAQ's
Speedbump is offline  
 
Reply With Quote Quick reply to this message
Old 09-13-2010, 06:54 AM  
oldman55
Junior Member
 
Join Date: Nov 2007
Location: Marion,In., Indiana
Posts: 7
Default

if you want to solder the hole shut you will need some silver solder, your friend should be able to get it where he works. If he can't get any I have also seen it at Tractor supply. as for the torch, if you can find one the pro's use the turbo torch is good up to about 5/8 line any bigger you can't get the pipe hot enough. you said you had some torches, honestly that is probably you best bet. just remember that you are brazing so no flux,that is why you put nitrogen though the lines is to assure a good clean bond.



__________________
oldman55 is offline  
 
Reply With Quote Quick reply to this message
Reply


Quick Reply
Message:
Options

Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Trackbacks are Off
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter DIY Home Repair Forum Replies Last Post
Basic Soldering of copper pipe Nestor_Kelebay Plumbing Forum 37 03-02-2013 01:50 PM
Has the price of copper wire come down? travelover Electrical and Wiring 1 01-04-2009 01:51 PM
Changing galv to copper for shower. DIYGUY Plumbing Forum 3 06-06-2007 06:42 PM
Punctured hole in Copper Tubing dkchatterton HVAC 3 01-20-2007 02:39 PM
Installing copper pipe PAULYBOY Plumbing Forum 23 07-17-2006 12:13 PM