Quote:
Originally Posted by John1
My blower on my furnace (Trane XE90) won't come on when the A/C (Trane XL1200) is on. If I turn the A/C off and put the fan to manual, the fan comes on with no problem. The condencer on the A/C unit will run, but not the inside fan on the furnace. Do I need to replace the board? Need help
|
Most of the electronic boards today, The green post is for manual fan runs the fan on a low speed like the heating speed. When you turn on cooling, the power comes back to the y post which goes to the condenser and also to a different relay that starts the blower on a faster speed. So i would say you have a bad board. Paul