  • Posted in thread: York Stellar Erratic Starting on 01-07-2011 at 07:24 PM
    PaulIt was the stack inducer fan.Installed new on/off power switch tonight.With both fans
    running now getting 24.7v @ transformer, 24.2v back from thermostat and 24.0v @ fan limit
    switch and 119.2v on...

  • Posted in thread: York Stellar Erratic Starting on 01-06-2011 at 08:02 PM
    It's a 40VA transformer.With the vent blower off I was getting 26.5 volts out, vent blower on
    24.6 volts out and 24.1 volts back from thermostat.I got this after I took the120 power on/off
    switch out ...

  • Posted in thread: York Stellar Erratic Starting on 01-05-2011 at 07:57 PM
    Paul,Think you might be on to it.I see my battery backup on computer had kicked on today
    although the furnace didn't completely fail.I just read 26.7 volts at transformer with vent
    blower off, dropped...

  • Posted in thread: York Stellar Erratic Starting on 01-04-2011 at 07:59 PM
    Thanks paul52446m.The gas valve & the electronic board have both been changed out.When it fails
    the gas valve stays open less than a second and the burner(s) nearest the flame sensor don't
    light.I am ...

  • Posted in thread: York Stellar Erratic Starting on 12-25-2010 at 05:58 AM
    Had already checked the water drain as well as the vent fan intake and exhaust pipe for
    obstructions. Also checked the heat exchanger for cracks. and checked for carbon monoxide in
    the vent pipe.Servi...

  • Posted in thread: York Stellar Erratic Starting on 12-23-2010 at 08:26 AM
    I am also having same intermittent problem with my York 15 year old York. Vent fan comes on,
    gas valve opens, spark igniter heats up, burners do not light all the way across, gas valve
    closes. Most of...