Default In-Slab Drain -- Sanity Check

Hey guys,

I'm getting close to having my inspection (Alberta, Canada) for the below-grade plumbing and I'd like to get some of you fine folks to double-check my work. Some of it (the parts that are already in use) are cemented, but some of what you see is just dry-fitted.

There's a lot going on in a pretty small space. There will be a wall almost bisecting the picture. Bathroom on right, Laundry / Furnace room on left.



Some comments:
- Backflow preventer is at where the drain exits the house.
- There is a roughly 1/4"/ft slope throughout the horizontal.
- The vertical stack, the vent at the shower drain and the stub for the basement kitchen will all be inside the future 2x6 wall, with access panels to the cleanouts.
- The tub drain and overflow are not at the right height...it will end up much closer to the bottom of the picture once it is trimmed.
- The 1 1/2" vent are going to be attached to the main stack above the overflow level upstairs.
- All the fixtures (except for the toilet) have p-traps.
- The center of the toilet flange will be 12" from the finished wall and the tub drain will be setup for a 60" x 30" tub.

One of my concerns is the 180 degree turn for some of the pipes. I know it's not idea, but is it strictly forbidden, or does it depend on the inspector/locale?

The other concern is venting. I hope I have adequate venting, but I could be wrong. I'm not 100% clear on those requirements. The basement kitchen line will have it's own vent closer to the end.

Anything I should change or consider before cementing up the rest and booking an inspection? Thanks in advance.

Here's the same picture without labels and also another.



__________________
Jordan
Edmonton, Canada
wraezor is offline  
KULTULZ Likes This 
Reply With Quote
Old 11-03-2016, 10:28 PM  
nealtw
Contractor retired
 
nealtw's Avatar
Join Date: Nov 2010
Location: Upper Fraser Valley, British Columbia
Posts: 21,760
Liked 2517 Times on 2212 Posts
Likes Given: 4212

Default

Frodo should be along so I will leave those details for him.

I don't know what code is but out here, the pan under the water tank and the dribble valve feed the trap below the floor.


nealtw is offline  
 
Reply With Quote
Old 11-04-2016, 11:42 PM  
frodo
Senior Member
 
frodo's Avatar
Join Date: Aug 2008
Posts: 2,698
Liked 979 Times on 771 Posts
Likes Given: 365

Default

.....................add a vent after the back water valve /before the toilet

tub looks like 1.5..needs to be 2''

move d.combo back, to many turns, paper will cause clogs
Click image for larger version

Name:	0TafX0r.jpg
Views:	69
Size:	76.1 KB
ID:	12794  
__________________
Cogito, ergo armatus sum.

My advice is free, If I have helped you and you wish to help the site out with a gift
use this link
http://www.houserepairtalk.com/forum/...faq=supporting

Last edited by frodo; 11-04-2016 at 11:44 PM.
frodo is offline  
 
Reply With Quote
Old 11-05-2016, 10:03 AM  
cmccomb
Junior Member
Join Date: Nov 2016
Posts: 2
Default

Is there a way to finish that out to where you don't have to cement it in that way you can get back to it if need be? You pour cement and it's not right you're in for a world of sweat
cmccomb is offline  
 
Reply With Quote
Old 11-05-2016, 02:40 PM  
wraezor
Homeowner
Join Date: Aug 2016
Location: Edmonton, Alberta
Posts: 8
Liked 1 Times on 1 Posts
Likes Given: 2

Default

Thank you for the feedback, sirs. May I get some clarification on the comments.

- What part of the tub drain needs to be 2"? From the p-trap on? The drain/overflow assembly I bought is all 1 1/2".

- You suggest another vent down from the toilet. Doesn't the 3" vertical stack to the roof provide that as well?

- And sorry, what is the d. combo?

Thanks.
__________________
Jordan
Edmonton, Canada
wraezor is offline  
 
Reply With Quote
Old 11-05-2016, 05:46 PM  
frodo
Senior Member
 
frodo's Avatar
Join Date: Aug 2008
Posts: 2,698
Liked 979 Times on 771 Posts
Likes Given: 365

Default

Quote:
Originally Posted by wraezor View Post
Thank you for the feedback, sirs. May I get some clarification on the comments.

- What part of the tub drain needs to be 2"? From the p-trap on? The drain/overflow assembly I bought is all 1 1/2".

- You suggest another vent down from the toilet. Doesn't the 3" vertical stack to the roof provide that as well?

need the vent behind the toilet not in front, the waste stack for the 2nd floor is a waste stack not a vent stack

- And sorry, what is the d. combo?

double combination




Thanks.
....................
Click image for larger version

Name:	Untitled.jpg
Views:	64
Size:	26.5 KB
ID:	12805  
__________________
Cogito, ergo armatus sum.

My advice is free, If I have helped you and you wish to help the site out with a gift
use this link
http://www.houserepairtalk.com/forum/...faq=supporting
frodo is offline  
2
People Like This 
Reply With Quote
Old 11-07-2016, 04:08 AM  
frodo
Senior Member
 
frodo's Avatar
Join Date: Aug 2008
Posts: 2,698
Liked 979 Times on 771 Posts
Likes Given: 365

Default

Quote:
Originally Posted by wraezor View Post
Thank you for the feedback, sirs. May I get some clarification on the comments.

- What part of the tub drain needs to be 2"? From the p-trap on? The drain/overflow assembly I bought is all 1 1/2".

- You suggest another vent down from the toilet. Doesn't the 3" vertical stack to the roof provide that as well?

- And sorry, what is the d. combo?

Thanks.

sorry, did not have time for a lengthy answer, I have been busy
the double combination in your picture has a 90 degre fitting attached to it and a 45 to pick up a toilet,
WAY to many bends you are allowed up to 135 degrees before a clean out is required to claean out the line you are at 225...
altho you are legal. you are into what i call not a good practice.

to fix it,

move the combo to where the combo for the upstairs is [switch spots]
you will have to knock the dirt off that corner..but, you can handle it.

also..you need a vent BEFORE the toilet. and the waste stack for upstairs is a waste stack, not a ven.
so add a vent.

what you should wind up with is 4x2 combo,4'' d wye, 4x3 combo
in that order for the toilet and upstairs
Click image for larger version

Name:	shower.jpg
Views:	62
Size:	23.2 KB
ID:	12808  
__________________
Cogito, ergo armatus sum.

My advice is free, If I have helped you and you wish to help the site out with a gift
use this link
http://www.houserepairtalk.com/forum/...faq=supporting
frodo is offline  
wraezor Likes This 
Reply With Quote
Old 11-11-2016, 06:18 PM  
wraezor
Homeowner
Join Date: Aug 2016
Location: Edmonton, Alberta
Posts: 8
Liked 1 Times on 1 Posts
Likes Given: 2

Default

That's very helpful, thanks. I'm sorry I didn't take a better picture of what's going on on the other side. I can definitely make the change to get the additional vent line in, and connect into the toilet closer to the backwater valve as suggested.

Maybe this top-down will be helpful regarding the other side of the layout. I'm really not sure how else I get the drain line (fixtures: floor drain, washer, upstairs kitchen) from the top of the photo into the main sewer line. Can I do that turn if I add another cleanout somehow?

__________________
Jordan
Edmonton, Canada
wraezor is offline  
 
Reply With Quote
Old 12-21-2016, 03:56 PM  
wraezor
Homeowner
Join Date: Aug 2016
Location: Edmonton, Alberta
Posts: 8
Liked 1 Times on 1 Posts
Likes Given: 2

Default

Hi guys,

Sorry to resurrect an old thread, but I've got one further hurdle to getting this solved. It is the washing machine.

How do I tie it into my main sewer line?

My main sewer line exits underneath the north exterior wall. I have a backwater valve in line, right before it exits under the wall. The same north wall (5 feet away) will have a washing machine. In order to connect to the main sewer line before the backwater valve, I need to drain away from the wall and then turn essentially 180 degrees.


What is the best strategy for this? Can I put an extra cleanout flush with the floor to make the 180-ish degree turn kosher?

Here's a simplified illustration:


Thanks in advance. I really appreciate the help, since I feel I've gotten in over my head with this project.
__________________
Jordan
Edmonton, Canada
wraezor is offline  
 
Reply With Quote
Old 12-22-2016, 02:50 PM  
nealtw
Contractor retired
 
nealtw's Avatar
Join Date: Nov 2010
Location: Upper Fraser Valley, British Columbia
Posts: 21,760
Liked 2517 Times on 2212 Posts
Likes Given: 4212

Default

You would likely want to add a vent too as your max is 60 inches ( I think)


nealtw is offline  
 
Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is On
HTML code is Off


Similar Threads
Thread Thread Starter DIY Home Repair Forum Replies Last Post
Roof design sanity check remout General Home Improvement Discussion 5 04-30-2015 04:47 PM
Request - Kitchen remodel sanity check McLovin General Home Improvement Discussion 6 08-24-2013 09:27 PM
Sanity Check - Prepping Walls for Painting/Tiling MyHouseIsADump Walls and Ceilings 3 08-05-2013 05:30 PM
Basement Floor Drain - Add check valve islander Plumbing Forum 0 04-24-2010 11:29 AM
Run new drain through or around slab KeninCharlotte Plumbing Forum 2 07-01-2006 07:17 PM