I have a new power pole on my 5 acre property. I need to run a 200Amp power from the pole to the house. The electrician used 4/0 aluminum from the breaker on the pole to the WIP on the top of the power pole. He stated I need the same to go from the Pole to the house underground. That is fine, however I would prefer a copper run. I have 300 Feet from Pole to my house. I know I need to run 3 cables in a special PVC pipe, however what size should I use? Doesn't 2/0 copper = 4/0 Aluminum? That is what the internet seems to show. I know I will have a little drop over that long a run.. What is the best run for this situation?
Thanks.
XM
Thanks.
XM