Found the problem the main breaker when I was reading it earlier this week when it was working and bench checked it was fine. But when it tripped never went back to it I just reset it. I still was reading 120 from ground to each pole But not across on pole side where I suppose to get 240 I was...
Yeah that’s why I changed the breaker
I took all power leads off the bottom of breaker and connected 1 wire on each side of 120 straight to primary nothing on secondary and I’m getting 7 to 8v reading
Correct that’s without wire leads on secondary, been messing with since Tuesday it worked overnight Tuesday after changing transformer shut off that morning. That when I notice I didn’t have 24v turned main breaker off for 10 minutes the breaker back on it ran till it satisfied. Never have been...
I have a Goodman electric unit for 15 years. Had issue coming back from vacation I do have a nest thermostat that said e73 no power to rc. Check voltage at breaker and transformer on secondary side wasn’t getting 24v. Even when I used straight wire to primary 240 and nothing connected on...